Requirements for building products under Fire Safety and Shelter Department
The Singapore Civil Defence Force (SCDF) places great importance in the selection of buildings products with respect to fire safety of buildings. These products might be in discrete forms such as fire doors and fire extinguishers, or they might be non-discrete in nature such as fire rated partition and glass blocks.
The proper selection and installation of these products ensure that the intent of the approved fire safety plans is achieved, namely that in a fire situation, occupants are able to evacuate to safety quickly, spread of smoke and fire is contained, fire protection systems are able to function as they should, and the SCDF is able to conduct its rescue and fire fighting operations.
Hence, SCDF have been dedicating a significant amount of their time and effort to ensure that there is an adequate level of control over products going into the buildings. SCDF has worked together with TÜV SÜD to implement the PLS as the vehicle of building products approval from the fire safety perspective. SCDF's new role in this approval process would be one of setting requirements and enforcement. Product control, such as type testing, batch testing, factory audit, market and factory surveillance, labelling, listing and publishing of listing directories would be carried out by TÜV SÜD under the PSB Product Listing Scheme.
The list of SCDF regulated fire safety products
With the implementation of the PLS, qualified persons (QPs) should select the fire safety products that are listed under the PLS to meet the requirement of the Fire Code. Products shall be constructed in accordance with the tested specimen. Materials used shall be identical with the test construction. Usage of the listed products need to comply with SCDF's Code of Practice for Fire Precautions in Buildings.
There shall be no modification to the prototype design. If modification is unavoidable due to site construction constraint or other reasons, satisfactory test/assessment report shall be submitted to TÜV SÜD for further consideration, verification and approval for the modification. The list of fire safety products and their requirements are as shown in the following table.
Product | Acceptable Standards | PLS Class | Labelling/ Marking |
|---|---|---|---|
1) Fire Alarm Panel | BS EN 54 Pt 2 & 4 | 1A or 1B | Labels issued by TÜV SÜD PSB |
2) Fire Pump | AS 2941 | 1A | Labels issued by TÜV SÜD PSB |
3) Fire-rated Partition (12) | |||
3.1) Compartment wall | BS 476 Pt 4/11 or EN 13501-1 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
3.2) Protected shaft enclosing lift (1) | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
3.3) Protected shaft enclosing staircase or services | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
4) Fire-rated Floor (1) | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
5) Fire-rated Ceiling (12) | |||
5.1) Compartmentation | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
5.2) Protection to steel beams that support RC floor (1) | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
5.3) Protection to timber/ steel flooring (1) | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
6) Fire-rated Enclosure/ spraying material (12) | |||
6.1) Protection to steel structure (1) (2) | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
6.2) Protection to fire fighting system ie sprinkler, rising mains, hydrant etc (3) | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
6.3) Protection to building services ie cables, sanitary pipes, chilled water pipes etc | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
7) Smoke Curtain (4) (12) | EN 13501-1 | 1B | Labels issued by TÜV SÜD PSB |
8) Fire-rated duct system, eg. Ventilation, Smoke-extraction and/or Kitchen Exhaust Ducting System (5) (12) | BS 476 Pt 4/11 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
9) Fire Extinguishing System for Kitchen Hood | UL 300 | 1A | Labels issued by TÜV SÜD PSB |
10) Fire Stopping Material (including Fire Rated Collar) | BS 476 Pt 20 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
11) Fire-rated Glass Block/ Partition/Panel (6) | BS 476 Pt 22 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
12) Exit sign (powered electrically) | SS 263 Pt 2 | 1A or 1B | Labels issued by TÜV SÜD PSB |
13 ) Emergency lighting (self-contained) | SS 263 Pt 2 | 1A or 1B | Labels issued by TÜV SÜD PSB |
14) Battery System (for exit signs and emergency lighting) | SS 563 Pt 1 & 2 | 1A or 1B | Labels issued by TÜV SÜD PSB |
15) Self-luminous Sign (powered by radioactive material) | BS 5499 Pt 2 | 1A or 1B | Labels issued by TÜV SÜD PSB |
16) Fire Hosereel | EN 671 Pt 1 | 1A or 1B | Labels issued by TÜV SÜD PSB |
17) Fire Fighting Hose | BS 6391 | 1A or 1B | Labels issued by TÜV SÜD PSB |
18) Auditorium Seats (7) | BS 5852 | 1B | Labels issued by TÜV SÜD PSB |
19) Fire Damper | For Fire Test: | 1B | Labels issued by TÜV SÜD PSB |
20) Fire-rated Door (13) | SS 332 Clause 4 or EN 1634-1 | 1A or 1B | Labels issued by TÜV SÜD PSB |
21) Bin/Linen Chute Door | BS 476 Pt 22 | 1A or 1B | Labels issued by TÜV SÜD PSB |
22) Fire-rated Lift-landing/ Dumb Waiter Door | BS 476 Pt 22 | 1B | Labels issued by TÜV SÜD PSB |
23) Fire Shutter/Fire Curtain | SS 489 Clause 3.5 & 4 or EN 1634-1 (the fire shutter/fire curtain shall close at between 10 sec and 30 sec) | 1B | Labels issued by TÜV SÜD PSB |
24) Fire-rated Hopper / Hatch door | BS 476 Pt 22 or EN 1634-1 or AS 1530 Pt 4 | 1A or 1B | Labels issued by TÜV SÜD PSB |
25) Portable Fire Extinguisher | SS EN 3-7 | 1A or 1B | Labels issued by TÜV SÜD PSB |
26) Fire-rated Cables | SS 299 Pt 1 or | 1A | Mark printed on cables |
27) Intumescent Coating System (for protection to steel structure) (8) | BS 476 Pt 21 (for fire-resistance test) | Declaration of Compliance issued by TÜV SÜD PSB | |
28) Landing Valve | BS 5041 Pt 1 | 1A or 1B | Labels issued by TÜV SÜD PSB |
29) Breeching Inlet | BS 5041 Pt 3 | 1A or 1B | Labels issued by TÜV SÜD PSB |
30) Raised Floor Panel (9)(10) | BS 476 Pt 4/11 or EN 13501-1 (applicable to the core material of composite construction) | 2 | No label |
31) Material for Wall/Ceiling Construction (9) | BS 476 Pt 4/11/7/6 & 7 | 2 | No label |
32) Thermal Insulation Material (9) | BS 476 Pt 4/11/7/6 & 7 | 2 | No label |
33) Finishing material for wall/ ceiling (9) | BS 476 Pt 4/Pt 7/Pt 6 & 7 | 2 | No label |
34) Roof Covering Material (9)(14) | BS 476 Pt 4/Pt 7/Pt 6 & 7 | 2 | No label |
35) Composite Panel ( Cladding to External Wall ) | BS 476 Pt 4/Pt 6 & 7/EN 13501-1 (applicable to the core material of composite construction) | 2 | No label |
36) UPVC Window Frame Material (11) | ASTM D635 | 2 | No label |
37) Door Closer(13) / other hardware | SS 332 Clause 5 | 1A | Mark printed on closer |
38) Household Shelter Door | FSSD's requirements | 1A | Labels issued by TÜV SÜD PSB |
39) Storey Shelter Door | FSSD's requirements | 1A | Labels issued by TÜV SÜD PSB |
40) Cross / Glued Laminated Timber | EN 1363 | 1A | Declaration of Compliance issued by TÜV SÜD PSB |
41) Materials for use in Photovoltaic (PV) Modules | IEC 61730-2 Cl 10.8 or UL 790 | 2 | No label |
42) Materials for Flooring | EN 13501-1 | 2 | No label |
Labels and declaration of compliance
Labels

Declaration of Compliance

Note :
1. ASTM E119 and NFPA 251 are not acceptable for load-bearing elements.
2. To comply with requirements stipulated under clause 3.3.7 of Fire Code 2007.
3. The insulation criterion shall be min. 30 minutes.
4. Class ''0'' surface spread of flame.
5. Insulation criteria of ducting system shall have both internal and external rating.
6. Permitted for use in sprinkler protected buildings only.
7. Applies to upholstered seats and plastic seats, either in fixed position or retractable type.
8. Weathering tests shall include the following:
- Heating test
- Washing test
- Sulphur dioxide test
- Humidity test
- Natural weathering test(for external use)
- The requirements as stipulated under Clause 3.15.1 of the Fire Code
9. Materials containing plastics would not be allowed.
10. Combustible core is permitted only in sprinkler protected buildings.
11. Installation of UPVC window frame shall conform to the FSSD's Guidelines.
12. Materials used are listed for BS 476: Pt 4/11 or 6/7 under PLS Class 2.
13. Door closers used in fire-rated door are separately listed under PLS Class 1A
14. Insulating lining shall also achieve Class "1" flame spread rating